WSS INVERTER MZ2000 series AC VFD
WSS INVERTER MZ2000 series Compact Vector Control
– Senseless flux vector control (VC), V/F (Voltage/Frequency) control
– Overload capacity is 150% (100%) of the rated current, 3s for 180% of the rated current
– There are ten auxiliary frequency sources. It can implement fine tuning of auxiliary frequency and frequency synthesis
– Suppot PM motor (MZ2000 T sereies)
Power range
MZ2200 : 220V / 0.25 ~ 3.7kW
MZ2400 : 380V / 0.75 ~ 450kW
Description
Technical specification
Item |
specification |
||
Standard Functions | Control mode | V/F (Voltage/Frequency) control Senseless flux vector control (VC) | |
Maximum frequency | Vector control: 0 – 300Hz; V/F control: 0 – 3200Hz | ||
Carrier frequency | 1.0 – 16.0kHz; The carrier frequency is automatically adjusted based on the load features. | ||
Input frequency solution | Digital setting: 0.01Hz Analog setting: 0.025% of maximum frequency | ||
Startup torque | G type: 0.5Hz / 150% (VC) P type: 0.5Hz / 100% (VC) | ||
Speed range / stability accuracy | 1:100 (VC) / ± 0.2% (VC) | ||
Torque control accuracy | ± 0.2% | ||
Overload capacity | G type : 60s for 150% of the rated current, 3s for 180% of the rated current. | ||
Torque boost | Auto boost Customized boost 0.1% – 30.0% | ||
V/F curve | Line V/F curve Multi-point V/F curve N-power V/F curve (1.2-power, 1.4-power, 1.6-power, 1.8-power, square | ||
V/F separation | Two types: complete separation; half separation | ||
Ramp mode | Sraight-line ramp; S- curve ramp Four groups of acceleration/deceleration time with the range of 0.0 – 6500.0s | ||
Standard Functions | DC braking | DC braking frequency: 0.00Hz to maximum frequency Braking time: 0.0 – 100.0s; Braking action current value: 0.0% – 100.0% | |
JOG control | JOG frequency range: 0.00 – 50.00Hz JOG acceleration/deceleration time: 0.0 – 6500.0s | ||
Onboard multiple preset speeds | It implements up to 16 speeds via the simple PLC function or combination of termial states. | ||
Onboard PID | It realized process-controlled closed loop control system easily. | ||
Auto voltage regulation (AVR) | It can keep constant output voltage automatically when the mains voltage changes. | ||
Overvoltage/ Overcurrent stall control | The current and voltage are limited automatically during the running process so as to avoid frequent tripping due to overvoltage / over current | ||
Torque limit and control | It can limit the torque automatically and prevent frequent over current tripping during the running process. | ||
Power dip ride through | The load feedback energy compensates the voltage reduction so that the AC drive can continue to run for a short time. | ||
Rapid current limit | It helps to avoid frequent over current faults of the AC drive. | ||
High performance | Control of asynchronous motoris implemented through the high-performance current vector control technology. | ||
Timing control | Time range: 0.0 – 6500.0 minutes | ||
Communication methods | RS485 (MODBUS-RTU) | ||
Protection mode | Motor short-circuit detection at power-on, input/output phase loss protection, over current protection, overvoltage protection, under voltage protection, overheat protection and overload protection. | ||
Input and Output | Input terminal | 6 digital input terminals, one of which supports up to 100kHz high-speedpulse input. 2 analog input terminals, one of which only supports 0 – 10V voltage input and the other supports 0 – 10V voltage input or 4 – 20mAcurrent input. | |
Frequency source | Digital setting, analog voltage setting, analog current setting, pulse setting and serial communication port setting. | ||
Auxiliary frequency source | There are ten auxiliary frequency sources. It can implement fine tuning of auxiliary frequency and frequency synthesis. | ||
Running command source | Operation panel / Control terminals / Serial communication port. You can perform switchover between these sources in various ways. | ||
Output terminal | 1 digital output terminal; 1 relay output terminal 1 analog output terminal: that support 0 – 20mA current output or 0 – 10V voltage output. | ||
Keyboard | LED display | It displays the parameters. | |
Key locking and function selection | It can lock the keys partially or completely and define the function range of some keys so as to prevent mis-function. |